Place of Origin :Anhui,China
Brand Name :Litong Global
Certification :ISO9001
Model Number :LT-151029
Application :Overhead Transmission line
Surface Treatment :Draw Wire
Grade :High Tensile Strength
Al Content (%) :99.999%
Alloy Or Not :Non-alloy
Powder Or Not :Non-powder
MOQ :Negotiable
Price :Negotiable
Packaging Details :On Drum
Delivery Time :12 days after confirmed order
Payment Terms :TT/LC
Supply Ability :1000KM/day
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

ACSR-Bare Aluminum Conductor Steel Reinforced

Code Word

Size (AWG or KCMIL)

Stranding (Al/Stl)

Diameter (inches)

Weight Per 1000ft (lbs.)

Rated Strength (lbs.)

Resistance OHMS/1000ft.

Allowable Ampacity+ (Amps)

AL

Steel

Complete Cable

AL

Steel

Total

DC @ 20°C

AC @ 75°C

Turkey

6

6/1

.0661

.0661

.1980

24.5

11.6

36.1

1190

.641

.806

105

Swan

4

6/1

.0834

.0834

.2500

39.0

18.4

57.4

1860

.403

.515

140

Swanate

4

7/1

.0772

.1030

.2570

39.0

28.0

67.0

2360

.399

.519

140

Sparrow

2

6/1

.1052

.1052

.3160

62.0

29.3

91.3

2850

.254

.332

184

Sparate

2

7/1

.0974

.1298

.3250

62.0

44.7

106.7

3460

.251

.338

184

Robin

1

6/1

.1181

.1181

.3550

78.2

37.0

115.2

3550

.201

.268

212

Raven

1/0

6/1

.1327

.1327

.3980

98.7

46.6

145.3

4380

.159

.217

242

Quail

2/0

6/1

.1489

.1489

.4470

124.3

58.8

183.1

5310

.126

.176

276

Pigeon

3/0

6/1

.1672

.1672

.5020

156.7

74.1

230.8

6620

.100

.144

315

Penguin

4/0

6/1

.1878

.1878

.5630

197.7

93.4

291.1

8350

.0795

.119

357

Waxwing

266.8

18/1

.1217

.1217

.6090

250.3

39.2

289.5

6880

.0643

.0787

449

Partridge

266.8

26/7

.1013

.0788

.6420

251.7

115.6

367.3

11300

.0637

.0779

475

Ostrich

300.0

26/7

.1074

.0835

.6800

283.0

130.0

412.0

12700

.0567

.0693

492

Merlin

336.4

18/1

.1367

.1367

.6840

315.8

49.5

365.3

8680

.0510

.0625

519

Linnet

336.4

26/7

.1137

.0885

.7210

317.1

145.5

462.6

14100

.0505

.0618

529

Oriole

336.4

30/7

.1059

.1059

.7410

381.0

209.0

526.0

17300

.0502

.0613

535

Chickadee

397.5

18/1

.1486

.1486

.7430

373.1

58.5

431.6

9940

.0432

.0529

576

Brant

397.5

24/7

.1287

.0858

.7720

374.0

137.0

511.0

14600

.0430

.0526

584

lbis

397.5

26/7

.1236

.0962

.7930

374.7

171.9

546.6

16300

.0428

.0523

587

Lark

397.5

30/7

.1151

.1151

.8060

375.0

247.0

622.0

20300

.0425

.0519

594

Pelican

477.0

18/1

.1628

.1628

.8140

447.8

70.2

518.0

11800

.0360

.0442

646

Flicker

477.0

24/7

.1410

.094

.8460

449.0

164.0

614.0

17200

.0358

.0439

655

Hawk

477.0

26/7

.1354

.1053

.8580

449.6

206.4

656.0

19500

.0356

.0436

659

Application:
Used as bare overhead transmission conductor and as primary and secondary distribution conductor and messenger support.ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.

Quality:
Production accroding to ASTM-B232,BS215-2,and IEC60189,DIN48201.

Material:
Conductor:AL1350 pure aluminum
Steel core:G1A or G2A steel wire
Zinc coating steel wire

Working Conditions:
Ambient temperature:Above -20°C
Working temperature:Not exceed 80°C
Laying bending radius:Not less than 30 times the cables outer diameter

Standards:
ASTM-B232 Standard specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
BS215-2 Aluminium conductors steel-reinforced -For overhead power transmission
DIN48204 Steel reinforced aluminum stranded conductors
IEC209 Aluminum stranded conductor steel reinforced


Inquiry Cart 0